BS5308 PAS 5308 Part 2 Type 2 Instrumentation Cable

Qty:
Add to Quote
Compare
Category:

Product Description

Designed to carry communication and control signals. BS 5308 cables are designed to form part of an intrinsically safe system.

  • Part 2 cables have an insulation of PVC.
  • Type 2 cables suitable for direct burial.
  • The PVC sheathing material has an OI above 30% and HCL below 15% and the LSZH material is of type LTS3. Collectively and individually screened pairs are available within the range.

Technical Specification

Conductor

Class 1 solid, Class 2 stranded or Class 5 copper conductor according to BS EN 60228 (previously to 6360)

Pairing

Two insulated conductors uniformly twisted together

Insulation

PVC (Polyvinyl Chloride) Type TM1according to BS EN 50363

Shielding

AL/PET (Aluminium/Polyester Tape)

Drain Wire

Tinned copper

Sheath

PVC (Polyvinyl Chloride) Type TM1 according to BS EN 50363

Rated Voltage [V]

300 / 500

Temperature Rating

Fixed: -30°C to +75°C

Minimum Bending Radius

Fixed: 18 x overall diameter

Sheath Colour

Blue / Black